Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM04972
Parcel: 125120810

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM04972
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the location of the vent to come off of the outlet pipe. [Original comment: Provide a vent for the sediment interceptor. Reference: Section 1003.9, IPC 2006.]
2. The bottom-access sediment trap requires at least 10" of clearance for maintenance; is that space available? [Original comment: Clarify the installation of the sediment trap, showing how the bottom-access interceptor will be able to be installed below the 3-compartment sink. Reference: Sections 106.3.1, 1003.2, and 1003.10, IPC 2006.]