Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM04972
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the location of the vent to come off of the outlet pipe. [Original comment: Provide a vent for the sediment interceptor. Reference: Section 1003.9, IPC 2006.] 2. The bottom-access sediment trap requires at least 10" of clearance for maintenance; is that space available? [Original comment: Clarify the installation of the sediment trap, showing how the bottom-access interceptor will be able to be installed below the 3-compartment sink. Reference: Sections 106.3.1, 1003.2, and 1003.10, IPC 2006.] |