Permit Number: T12CM04972
Parcel: 125120810

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM04972
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/13/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the location of the vent to come off of the outlet pipe. [Original comment: Provide a vent for the sediment interceptor. Reference: Section 1003.9, IPC 2006.]
2. The bottom-access sediment trap requires at least 10" of clearance for maintenance; is that space available? [Original comment: Clarify the installation of the sediment trap, showing how the bottom-access interceptor will be able to be installed below the 3-compartment sink. Reference: Sections 106.3.1, 1003.2, and 1003.10, IPC 2006.]
09/13/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/13/2012 GERRY KOZIOL WWM REVIEW Approved