Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04972
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/24/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Provide site plan SHEET A1 2. The 5% slope for the 2.5" floor change between the two spaces calculates for a run of 4'-2". Please correct the run of the sloped area accordingly, two places. SHEET A4 3. At detail 2, please swing the shower door out as per ICC A117.1, Section 603.2.3 and increase the corridor width to 4'-0" as per door clearances 404.2.3.1 (f). END OF REVIEW |
| 08/28/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the installation of TD1; it is specified as having a 3" waste but detail 3/P3.1 indicates a 2" trap and fixture drain. Reference: Section 106.3.1, IPC 2006. 2. If the shower does not have a pre-fabricated receptor, provide details to show that the construction of the receptor complies with the requirements of Section 417.5.2, IPC 2006. 3. Clarify the reason for relocating the backwater valve and show how the new location meets the requirements of Section 715.1, IPC 2006, as amended by the City of Tucson. 4. Provide a vent for the sediment interceptor. Reference: Section 1003.9, IPC 2006. 5. Show how maintenance access will be provided for the lint trap, LT-1. Reference: Section 1003.10, IPC 2006. 6. Clarify the installation of the sediment trap, showing how the bottom-access interceptor will be able to be installed below the 3-compartment sink. Reference: Sections 106.3.1, 1003.2, and 1003.10, IPC 2006. 7. Show the size, slopes (for horizontal conductors), routing, and termination points for the roof drain and overflow roof drain leaders. Provide calculations to show that the size (i.e. width) of the scuppers is adequate. Reference: Sections 106.3.1, 1106, and 1107, IPC 2006. |
| 08/29/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/31/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the sequence of operation for the new restroom exhaust fans. According to the exhaust fan schedule, the fans are not controlled by the EMCS which conflicts with the sequence of operation shown on sheet M3.1. Reference: Section 106.3.1, IMC 2006. 2. Provide a site plan indicating the termination locations of the exhaust ducts (paint booth and clothes dryer) in relation to the property line, forced-air inlets and building openings. Reference: Section 501.2.1, IMC 2006. 3. Provide listing information for the specified tubeaxial fan for the paint booth. Reference: Section 502.7.3.6, IMC 2006. |
| 09/05/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: BOOKMAN'S RECREATION EXCHANGE (52FU'S) 2: NEED WATER METER UPSIZING FORM FROM WATER SUPPLIER FOR SEWER CONNECTION FEE CALCULATION (EXISTING 2" WATER METER PER DRAWING P1.2) 3: CONNECTING TO EXISTING BUILDING SEWER PER PERMIT #25053 DATED 7/18/88 AND PERMIT PT97S00434 DATED |
| 09/07/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |