Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM04879
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/10/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/16/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/22/2012 | RMYERS1 | WATER | REVIEW | Approved | |
08/22/2012 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Approved | |
08/24/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations to verify that the structure is capable of supporting the fan coil unit FC-1. Reference: Section 302.1, IMC 2006. 2. Provide structural details to show how the fan coil unit FC-1 is to be connected to the building structure. Reference: Section 302.1, IMC 2006. 3. Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Coordinate the building components used in the analysis with those shown on the drawing (e.g. include entry doors). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 4. Show the size, routing, and termination of the condensate drain for FC-2. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson. 5. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. |
08/27/2012 | LAITH ALSHAMI | ENGINEERING | REVIEW | Denied | Will be approved once Development Package DP12-0124 is approved. |
08/30/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/31/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/04/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/05/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
09/05/2012 | CPIERCE1 | REJECT SHELF | Completed |