Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM04879
Parcel: 133170630

Address:
350 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04879
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2012 MARTIN BROWN FIRE REVIEW Approved
08/16/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/22/2012 RMYERS1 WATER REVIEW Approved
08/22/2012 RICK MYERS PLUMBING-COMMERCIAL REVIEW Approved
08/24/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural calculations to verify that the structure is capable of supporting the fan coil unit FC-1. Reference: Section 302.1, IMC 2006.
2. Provide structural details to show how the fan coil unit FC-1 is to be connected to the building structure. Reference: Section 302.1, IMC 2006.
3. Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Coordinate the building components used in the analysis with those shown on the drawing (e.g. include entry doors). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
4. Show the size, routing, and termination of the condensate drain for FC-2. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson.
5. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
08/27/2012 LAITH ALSHAMI ENGINEERING REVIEW Denied Will be approved once Development Package DP12-0124 is approved.
08/30/2012 STEVE SHIELDS ZONING REVIEW Approved
08/31/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/04/2012 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/05/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
09/05/2012 CPIERCE1 REJECT SHELF Completed