Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM04806
Parcel: 11712087C

Address:
1 E BROADWAY BL

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM04806
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2012 KEN BROUILLETTE FIRE REVIEW Approved
11/14/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1.10; CMU WALL REINFORCING SCHEDULE: SHOULD THE VERTICAL REINFORCING "TYPICAL THROUGHOUT" HAVE A SPACING ALONG WITH THE #5 DESIGNATION? VERIFY THE CALCULATIONS (SHEETS 87-116) INDICATE 24" O.C.
2. SHEET S1.10; FOOTING SCHEDULE: REVISION 4 INDICATES FOOTING F2 HAS BEEN REVISED. HOWEVER, THE PREVIOUSLY APPROVED PLANS INDICATE F2 IS UNCHANGED. CLARIFY.
3. SHEET S1.10 (FOOTING SCHEDULE); STRUCTURAL CALCULATIONS: CALCULATIONS FOR FOOTINGS F3, F7, AND F8 (AT THE ELEVATORS AND STAIRS) WERE NOT LOCATED IN THE REVISED CALCULATIONS. VERIFY.
4. SHEET S2.0; FOUNDATION PLAN: ADD THE F3 FOOTING DESIGNATION TO THE PLAN AT THE ELEVATORS.
5. SHEET S3.5; FRAMING PLAN: SHOULD THE CLOUDED BOX (Fe 108K (4T)) IN THE SOUTHEAST CORNER INCLUDE THE VERBIAGE 'ADDITIONAL TENDONS' ? VERIFY.
6. SHEET S3.14; DETAIL G: THIS DETAIL CUT WAS NOT LOCATED ON ANY OF THE SHEARWALL ELEVATIONS. VERIFY.
7. GENERAL: PROVIDE TWO SETS OF STRUCTURAL CALCULATIONS.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/16/2012 ROBERT SHERRY WATER REVIEW Approved
11/16/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Verify the scheduled air flow for EF-1. It is shown as 250 CFM (continuous) which seems very high for 4" duct.
11/16/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T12CM04806
1 E. Broadway

We do not have a copy of previous approved plans, there was no revision sheets explaning changes and why they were made.
Provide previous approved plans or provide revision sheets indicating the changed made and for what reason.


Ray T Majuta
Elect Plan Review
PDSD, C of Tuc
11/05/2012
Ray.Majuta@tucsonaz.gov
11/16/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the presence of a floor drain in the boiler equipment room; a floor sink (P-8) appears in detail 5/P302 but not on any plumbing floor plans. Similarly, the waste piping for the 2" standpipe located in the boiler room approximately 11'-0" south of column F-3 is not shown on the plumbing floor plans. Reference: Section 103.2.3, UPC 2006 and Section 1004.6, IMC 2006.
2. Clarify the titles for the plumbing isometrics; the 7th floor has reappeared. (see also detail 1/P302)
11/20/2012 TERRY STEVENS ZONING REVIEW Denied Zoning cannot approve the building plan until strutural and plumbing have approved the plan. This review can be done over the counter by setting an appoiontment with me.
11/21/2012 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved Will stamp when plans are ready - all reviewers are approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/26/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed