Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T12CM04619
Parcel: 126134810

Address:
4635 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T12CM04619
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2012 KEN BROUILLETTE FIRE REVIEW Denied 1. Spoke to Arct.- I told him that the building area is over the 12K threshold for S-1 Fire Area and without a fire barrier installed, we need to use the exterior walls to determine square footage the fire area for the S-1. He will look into this requirement and determine if a fire barrier is necessary to reduce the fire area as outlined in Section 903.2.8.
2. Two exits are required in the workshop on page A1.2. The travel distance exceeds allowing only one exit per table 1019.2
09/12/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. As per the 2006 IBC, Section 903.2.8.1.2, a building with a repair garage may not exceed 12,000 s.f. with out a sprinkler system or fire separation. You may want to add a sprinkler system or extend the existing garage fire rated separation around the South end and the East side portion enclosed for the service area. Door number 16 will have to be a rated assembly.
2. Comment 3b: For your information only, in the Title of Table 1016.1, please reference the note "a" reference to Table 1019.2 which limits a one exit S area to a travel distance of 100'. This is a non enforceable 2006 IBC requirement because the auto repair workshop is not being modified.
3. Comment 8 and detail 2/C1.3: Detectable warnings are required only at marked crossings as per ICC A117.1, Sections 406.12, 13 and 14. They are not required at the end of an accessible parking aisle unless the accessible aisle is part of a marked crossing.
4. Comment 10: Please reference Section 903.2.8.1.2, 12,000 s.f. maxium area requirement.
5. Comment 13b: The existing door is shown swinging into the toilet room. The modified plans shows a new door, opposite jamb, swinging out. It needs to be numerated and added to the hardware schedule with a hardware set indicated.
6. Comment 16: Please confirm the operating weights of the roof mounted HVAC units to be removed and compair them to the operating weights of the replacement HVAC units and provide existing structural framing analysis and calculations if the new ones weigh more than the replaced units. Please note the results on the drawings.
END OF REVIEW
09/17/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/02/2012 TERRY STEVENS ZONING REVIEW Denied Zoning cannot approve the building plan until a development package has been submitted and approved.
10/02/2012 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Approved