Permit Number: T12CM04447
Parcel: 125120810

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM04447
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2012 MARTIN BROWN FIRE REVIEW Approved
08/09/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S2.0 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS (SHEETS 2 AND 38): COLUMN C3 IN THE CALCULATIONS IS DESIGNATED AS A 6X6X 3/8 ANGLE, WHILE THE DRAWING INDICATES C2 (HSS3X3X 1/4). CLARIFY.
2. SHEETS S2.0, S2.1, AND S2.2; KEYNOTES: THE KEYNOTES ARE HARD TO READ. REVISE.
3. SHEET S2.2 (ROOF FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEETS 4 AND 42): LINTEL LT1 IN THE CALCULATIONS IS DESIGNATED AS A HSS6X4X 3/16, WHILE THE DRAWING INDICATES LT1 (2 ANGLES 3 1/2 X 2 1/2 X 1/4). CLARIFY.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/27/2012 CINDY AGUILAR OUT TO CUSTOMER Completed