Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM04447
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/07/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/09/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S2.0 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS (SHEETS 2 AND 38): COLUMN C3 IN THE CALCULATIONS IS DESIGNATED AS A 6X6X 3/8 ANGLE, WHILE THE DRAWING INDICATES C2 (HSS3X3X 1/4). CLARIFY. 2. SHEETS S2.0, S2.1, AND S2.2; KEYNOTES: THE KEYNOTES ARE HARD TO READ. REVISE. 3. SHEET S2.2 (ROOF FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEETS 4 AND 42): LINTEL LT1 IN THE CALCULATIONS IS DESIGNATED AS A HSS6X4X 3/16, WHILE THE DRAWING INDICATES LT1 (2 ANGLES 3 1/2 X 2 1/2 X 1/4). CLARIFY. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/27/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |