Permit Number: T12CM04123
Parcel: 14028001B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM04123
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
07/10/2012 LOREN MAKUS ENGINEERING REVIEW Approved
07/10/2012 ERIC NEWCOMB ADA REVIEW Passed
07/10/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/10/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/11/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the slope of the steam supply tubing per the manufacturer's recommendations.
2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
07/11/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/11/2012 ROBERT SHERRY WATER REVIEW Approved
07/11/2012 MARTIN BROWN FIRE REVIEW Approved
07/11/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/12/2012 FRODRIG2 WWM REVIEW Needs Review