Permit Number: T12CM03122
Parcel: 11008305E

Address:
4685 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM03122
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2012 KEN BROUILLETTE FIRE REVIEW Approved
07/13/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the size of the condensate drains for the refrigeration evaporators in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson.
2. Clarify the basis for the ventilation calculations. The "zone & area" designations (e.g. "Health Corner Room") do not correspond to the room names on the floor plans - is this calculation for this building? Reference: Sections 106.3.1 and 403.3, IMC 2006.
3. The ventilation calculations appear to be based on ASHRAE 62.1 but they do not include sufficient information to be evaluated for a multiple-zone system. Provide the zone air distribution effectiveness (Section 6.2.2.2, ASHRAE 62.1-2004) and the calculations called for in Section 6.2.5, ASHRAE 62.1-2004. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
07/13/2012 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/13/2012 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
07/13/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the design of the venting for the new floor sinks and floor drains so that the vents rise vertically to at least 6" above the flood rim of the fixture being served prior to running horizontally. Reference: Section 905.4, IPC 2006.