Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM03122
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/13/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
07/13/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the condensate drains for the refrigeration evaporators in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson. 2. Clarify the basis for the ventilation calculations. The "zone & area" designations (e.g. "Health Corner Room") do not correspond to the room names on the floor plans - is this calculation for this building? Reference: Sections 106.3.1 and 403.3, IMC 2006. 3. The ventilation calculations appear to be based on ASHRAE 62.1 but they do not include sufficient information to be evaluated for a multiple-zone system. Provide the zone air distribution effectiveness (Section 6.2.2.2, ASHRAE 62.1-2004) and the calculations called for in Section 6.2.5, ASHRAE 62.1-2004. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. |
07/13/2012 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
07/13/2012 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
07/13/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the design of the venting for the new floor sinks and floor drains so that the vents rise vertically to at least 6" above the flood rim of the fixture being served prior to running horizontally. Reference: Section 905.4, IPC 2006. |