Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM03122
Parcel: 11008305E

Address:
4685 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM03122
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2012 KEN BROUILLETTE FIRE REVIEW Denied PLEASE INDICATE ON PLAN THE LOCATION OF THE EMERGENCY LIGHTING FIXTURES THAT WILL PROVIDE THE EGRESS LIGHTING.
INDICATE ON PLANS THE LOCATION OF THE EXIT SIGNS.
PLEASE RESUBMIT INDICATE PAGE NUMBERS TO FIND THESE CORRECTIONS.
06/07/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. The City of Tucson standards for lettering size on the construction drawings is a minimum of 3/32", actual height and includes both upper and lower case. Several of your drawing sheets do not comply with this standard. Please reveise all drawings that are non-compliant and resubmit.
2. Several floor plans and details show the existing conditions with a line weight that is so light it is hardly legable. It can certianly cause problems with our scanning system. Please review all details as to appropriate line weight thickness, revise and resubmit.
3. Please provide structural calculations for the wall mounted water bracket and the wall itself.
SHEET C-100
4. At note 03 30 28:
a. All new ramps are to comoply with ICC A117.1, Section 405 and 406 as applicable.
b. All marked crossings are to have detectable warning strips as required by ICC A117.1, Serctions 404.12, .13 and .14.
5. Please provide a large scale detail of the accessible parking:
a. The 4'-11 3/8" dimension is to be 11'-0"
b. The 7'-11" dimension is to be 8'-0"
c. Show slope in all accessible parkinmg areas to be a maximum of 2% in all directions as per section 405.2.
6. The curb ramp for the "Van Accessible" parking spaces is located in the middle of a couple of building columns.
SHEET G-011
7. The mounting height o the botttom of the main accessible parking sign is to be 7'-0" as per COT DOT requirements.
SHEET G-010
8. Please provide a list of the governing building codes including the 2006 IBC, Chapter 11 and ICC A117.1, 2003 Edition for accessibility requirements.

END OF REVIEW
06/12/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
06/18/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the size of the condensate drains for the refrigeration evaporators in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson.
2. Clarify the basis for the ventilation calculations. The "zone & area" designations (e.g. "Health Corner Room") do not correspond to the room names on the floor plans - is this calculation for this building? Reference: Sections 106.3.1 and 403.3, IMC 2006.
3. The ventilation calculations appear to be based on ASHRAE 62.1 but they do not include sufficient information to be evaluated for a multiple-zone system. Provide the zone air distribution effectiveness (Section 6.2.2.2, ASHRAE 62.1-2004) and the calculations called for in Section 6.2.5, ASHRAE 62.1-2004. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
06/18/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the plumbing code to be used for this activity. The Project Information on sheet G-010 refers to the most of the International Codes but does not include a plumbing code. This review has been made using the 2006 IPC.
2. Provide information to show how the proposed water heater is to be connected to the building structure. Reference: Sections 106.3.1 and 301.2, IPC 2006.
3. Provide a vacuum relief valve for the bottom-fed, storage-type water heater (EWH-1). Reference: Section 504.2, IPC 2006.
4. Indirect waste receptors shall be installed in readily accessible locations (e.g. the floor sink located completely under the new refrigerated case near C-2). Reference: Section 802.3, IPC 2006.
5. Revise the design of the venting for the new floor sinks and floor drains so that the vents rise vertically to at least 6" above the flood rim of the fixture being served prior to running horizontally. Reference: Section 905.4, IPC 2006.
06/18/2012 ROBERT SHERRY WATER REVIEW Approved
06/26/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM03122
4685 E Grant Rd
Walgreens TI

1. Sheet E-610, the letters and numbers on all panelboards are not ledgible, cannot be read or copied, please reprint clearly.
2. Per City of Tucson TI Submittal Requirements, each panel phase to show total KV or KVA and amperage total. The new total on service is to be provided.
3.E-111,circuit LP 3/34 shown on plan is shown as spre and no load provided in schedule.
4. Sheet E-131, circuits LPSP 2 and 10, how were the loads calculated >
5. Sheet E-421, provide a circuit and panel for note
26- 50 -35.

Ray T Majuta
Elect Plan Review,
PDSD, City of Tucson,
6/27/2012
Ray.Majuta@tucsonaz.gov
06/28/2012 GERRY KOZIOL WWM REVIEW Approved