Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM03078
Parcel: 13304003A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM03078
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; the revised drawing shows a drain line connecting to a vent. Reference: Section 311.4, UPC 2006. [Original comment: Clarify the connection point of the 2" drain from P-1A as shown in detail B/P-22 with respect to the location of the trap arm for P-2T. Reference: Section 311.4, UPC 2006.]
2. Comment not addressed. Show that the restroom floors slope toward the floor drains. Reference: Section 411.2, UPC 2006.
07/05/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
07/05/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2006.
07/10/2012 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review