Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM03078
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/05/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/05/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2006. |
| 07/05/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; the revised drawing shows a drain line connecting to a vent. Reference: Section 311.4, UPC 2006. [Original comment: Clarify the connection point of the 2" drain from P-1A as shown in detail B/P-22 with respect to the location of the trap arm for P-2T. Reference: Section 311.4, UPC 2006.] 2. Comment not addressed. Show that the restroom floors slope toward the floor drains. Reference: Section 411.2, UPC 2006. |
| 07/10/2012 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |