Permit Number: T12CM02728
Parcel: 13705293A

Address:
5160 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM02728
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/04/2012 JASON GREEN ENGINEERING REVIEW Denied Building Plan will be stamped approved upon aproval of the development plan package, DP12-0144.
09/18/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 1; CODE CHECK: THE NEW SHADE CANOPY IS LISTED ON THIS SHEET AS 1520 SF, WHILE THE STRUCTURAL DRAWINGS INDICATE A 40' X 40' STRUCTURE (1600 SF). CLARIFY.
2. SHEET S1.2: THE 30' X 40' STRUCTURE IS INDICATED ON THIS SHEET, BUT IS NOT INCLUDED IN THE PROJECT VALUATION, OR INDICATED ON THE SITE PLAN. CLARIFY.
3. STRUCTURAL CALCULATIONS: THE COVER SHEET INDICATES A 40' X 40' STRUCTURE AND A 30' X 40' STRUCTURE. IS THERE A SECOND STRUCTURE IN THIS PROJECT? VERIFY.
4. SHEET S2.1; DETAIL 101: THE DETAIL INDICATES THE CHAIN HAS A 3 TON CAPACITY. IS THIS FOR TENSION (UPLIFT)? WHAT IS THE SHEAR CAPACITY OF THE CHAIN, AND THE ACTUAL DESIGN SHEAR? VERIFY.
5. SHEET S2.1; TRUSSES "A", "B", AND "C": THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE LETTERING FOR THE VERTICAL WEB MEMBER SIZES.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/26/2012 TERRY STEVENS ZONING REVIEW Denied Zoning cannot approve the building plan until the development package has been approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/15/2013 CPIERCE1 REJECT SHELF Completed
12/28/2012 CPIERCE1 OUT TO CUSTOMER Completed