Permit Number: T12CM02660
Parcel: 11516019S

Address:
1365 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM02660
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: PROVIDE FULL SIZE PLAN INDICATING THE SOLAR SYSTEM LAYOUT ON THE ROOF, INCLUDING CLEAR DISTANCES FROM THE PANELS TO THE EDGE OF THE ROOF.
2. GENERAL: PROVIDE A DETAIL ON A FULL SIZE SHEET FOR THE CONNECTION OF THE SOLAR PANEL FRAME TO THE EXISTING ROOF, INCLUDING CONNECTION SIZE, QUANTITY, AND SPACING.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/09/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved