Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T12CM02660
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/01/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. STRUCTURAL CALCULATIONS; SHEET 2: THE STATEMENT IS MADE THAT "THE NEW PV SOLAR PANEL WEIGHT WILL REPLACE THE LIVE LOAD ON THE ROOF". HOW DOES THE ADDITION OF SOLAR PANELS TO AN EXISTING ROOF REMOVE THE LIVE LOAD? PROVIDE THE SECTION REFERENCE TO THE 2006 IBC THAT ALLOWS THIS LIVE LOAD REMOVAL. OTHERWISE, PROVIDE A REVISED ANALYSIS FOR THE ADDITIONAL LOAD FROM THE PV ON TO THE EXISTING ROOF. |
| 06/11/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM02660 1365 W Grant RD Photovoltaic System 1. City of Tucson Commercial Submittal Requirements--- minimun text size for lettering or numbering is 3/32". The plans are too small, also once plans approved they are recorded ,these are too small to record. 2. Currently we are under the 2005 NEC, please indicate this on electrical sheets. 3. Provide a fault current calculation to show the AIC level at the 80 amp overcurrent device at the service, what type of breaker is to be used to meet that fault level. Also please show how you arrived at the 19,400 Aic level at the PV(AC) disconnect, and how you arrived at the 10,000 Aic level at the Inverter. 4. Check with utility requirements for the PV meter, a neutral may be required. Ray T Majuta Electrical Plan Review PDSD, City of Tucson 6/11/2012 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/25/2012 | FERNE RODRIGUEZ | REJECT SHELF | Completed |