Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM02659
Parcel: 13304003A

Review Status: Completed

Review Details: OTHER

Permit Number - T12CM02659
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2012 MARTIN BROWN FIRE REVIEW Approved
05/31/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. STRUCTURAL CALCULATIONS: PROVIDE CALCULATIONS FOR THE LATERAL/UPLIFT LOADS ON THE PANELS, AND THE ADEQUACY OF THE PV CONNECTORS TO THE EXISTING ROOF TO RESIST THOSE LOADS.
06/07/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM02659
9415 E Wrightstown Rd
120 KW Photovoltaic System


1. Currently Tucson under the 2005 NEC, cover sheet indicates Project under the 2008 NEC, if under the 2008 NEC indicate on all electrical sheets. Jurisdiction allows use of 2008 as long as all electrical sheets marked.
2. As per 690.64(B),3-----GFP, Exception allows connecting to load side of GFP service provided there is GFP for equipment from all ground fault sources. Appears the new
200 amp 3p HFD Series Breaker with GFP does this,provide a specification sheet on this breaker indicating listing and approval for use in 1600 Amp Eaton SES.
3. 2008 NEC 690.64.(B).7 requires Inverter output connection to be positioned at oppisite load end from the input feeder location or main, how does this installation comply ?
4. Indicate AIC rating for PV disconnect after Main Service,
item 3 on Sheet E1.3.

Ray T Majuta
Electrical Plan Review
PDSD, City of Tucson,
6/8/2012
Ray.Majuta@tucsonaz.gov
I

Final Status

Task End Date Reviewer's Name Type of Review Description
06/12/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed