Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM01566
Parcel: 14043013B

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T12CM01566
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/27/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/27/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/28/2012 SHANAE POWELL APPROVAL SHELF Completed
11/28/2012 SHANAE POWELL OUT TO CUSTOMER Completed