Permit Number: T12CM01566
Parcel: 14043013B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM01566
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A4.4
1. Detail 2 does not show accessible urinal.
SHEET A4.6
2. Detail 1 shows accessible urinal in an alcove with one side deeper than 2'-0". In this situation ICC A117.1, Sections 605 and 305.7 requires a 3'-0" wide clear urinal stall.
SHEET S3.1
3. Provide structural calculations for new HVAC load and framing on existing structural framing.
SHEET S4.0
4. Provide structural calculations fo all new steel framing and concrete foundations.
END OF REVIEW
07/11/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the size of the common condensate drain pipes shown on sheet M2.3 per Section 307.2.2, IMC 2006, as amended by the City of Tucson.
07/11/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide additional cleanouts in drainage pipe for each aggregate horizontal change of direction exceeding 135 degrees (see soil and vent riser diagram 2/M8.1). Reference: Section 707.5, UPC 2006.
2. Provide cleanouts sized per Section 707.11, UPC 2006 (see soil and vent riser diagram 2/M8.1).
07/23/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed