Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM01566
Parcel: 14043013B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM01566
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed; any slope for the restroom floors is not shown on the architectural drawings. [Original comment: Show that the restroom floors slope toward the floor drains. Reference: Section 411.2, UPC 2006.]
2. On sheets M3.1 and M3.2, the building drains (e.g. 2" SS and 4" SS) are shown connecting to the "(E) Main SD"; sanitary drains shall not be connected to storm drains (SD) under any circumstances. [Original comment: Show the location of the two-way cleanouts (indicated on sheets M8.1 and M8.2) on the plumbing plans. Two-way cleanouts may be installed at the junction of the building drain and the building sewer but are not required if an upper terminal cleanout is installed. Reference: Sections 707.4 and 707.6, UPC 2006.]
3. The revised detail 14/M6.2 shows the ice machine draining to an indirect waste receptor located within a cabinet. An indirect waste receptor may not be located inside of a cabinet or in any location in which they are not readily accessible and visible for inspection and cleaning. Reference: Section 804.1, UPC 2006. [Original comment: Revise the installation of the ice machine drains to be indirectly connected to the sanitary drain system using an air gap. Provide separate indirect waste pipes for the ice maker itself and for the ice storage bin. Reference: Sections 801.2.3 and 801.5, UPC 2006.]
05/09/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify keynotes 7/m3.1 and 17/m3.1: what is the "WAS collection pipe" into which the condensate is to terminate? Reference: Section 106.3, IMC 2006.
05/23/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/29/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved