Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM00254
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/03/2012 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 02/03/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 02/03/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 02/03/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/03/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/03/2012 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 02/03/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/03/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 02/08/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A2 (DETAIL 2); SHEET S1.1 (DETAIL 2): THE FOOTING SIZES AND REINFORCING DIFFER ON THE TWO DETAILS. COORDINATE. 2. SHEET A2; ELEVATION 1: PROVIDE THE RAMP SLOPE ON THE ELEVATION PER THE IBC SECTION 1010.2. 3. SHEET A2; DETAIL 2: PROVIDE THE RAMP CROSS SLOPE ON THE DETAIL PER THE IBC SECTION 1010.3. 4. SHEET A2; DETAIL 2: PROVIDE THE RAMP WIDTH. 5. SHEET S1.0: PROVIDE STRUCTURAL CALCULATIONS FOR THE NEW OPENING AND FRAMING IN THE EXISTING WALL. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/08/2012 | RONALD BROWN | ADA | REVIEW | Passed | |
| 02/08/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |