Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM00223
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2012 | CARL SCHULTZ | FIRE | REVIEW | Approved | |
| 05/03/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/04/2012 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: O'Reilly Auto Parts - 51 S. Pantano Road T12CM00223 Building Plan (2nd Review) TRANSMITTAL DATE: May 04, 2012 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning can not approve the building plan until the development package has been approved. 7. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 05/11/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/11/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed; no expiration date has been added to the seals. [Original comment: Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).] 2. Comment not addressed. [Original comment: Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.] 3. Comment not resolved. Note 1 on the Roof Secondary Plan states: "Purlin design is based on floor-mounted air handling units. If any air handling units are to be located on the roof, contact BMC for review of the roof secondary members". [Original comment: Provide structural calculations to verify that the roof is capable of supporting the condensing units and Z-purlins are capable of supporting the fan coil units. Reference: Section 302.1, IMC 2006.] |
| 05/11/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; note the required size of the downspouts on the drawings (the sizes are not on the pre-engineered metal building drawings either). [Original comment: Revise the downspout sizing based Table 11-1, UPC 2006. The 2006-edition of Table 11-1, UPC 2006 limits a 3" downspout to a tributary area of 2,147 square feet (earlier editions, such as the 1994 edition, did allow 2,930 square feet of tributary area to be drained with a 3" downspout). Reference: Section 1101.11.1 and Table 11-1, UPC 2006.] |
| 05/24/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. OREILLY AUTO PARTS - DP12-0014 2. NEED PCRWRD REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - CHAD AMATEAU 740-6547 3. NEED PCRWRD MANHOLE CONSTRUCTION PERMIT REVIEW & APPROVAL FRONTS 15" PUBLIC SEWER DENICE ELLE 740-6369 |
| 05/25/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM00223 51 S Pantano RD New Blgd, O'Reilly Auto Parts The electrical plans have been denied for the following: 1. All new electrical services must be underground.The requirement for overhead may be waived by the Building Official if esixting buildings on the block are served with overhead. This must be requested through the Building Official seperately. Per City of Tucson Ord# 10417 to the 2006 IBC. 2. Compliance with The City of Tucson Outdoor Lighting Code must be made through a calculation showing lumen (of all outdoor fixtures total) allowance per size of site as required per City of Tucson Ord # 10963. Can be found on City's website under Development Services,then Codes,Standards and Ordinances. 3. Sheet ES1 of 3, please explain the meaning of "CT" in the EMS Interface Requirements , looking for meaning of "CT" in panel MP and why such higher amperage values. 4. Explain Panel E as an emergency panel, how will this become energized upon utility failure ? Ray T Majuta Electrical Plan Review PDSD, City of Tucson 5/25/2012 Ray.majuta@tucsonaz.gov |
| 05/25/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | DP/Site must be approved before the building plans are approved. |