Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11OT02244
Parcel: 124120230

Review Status: Completed

Review Details: C OF O

Permit Number - T11OT02244
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
12/05/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved