Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM03806
Parcel: 130140390

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T11CM03806
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2012 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 01/05/2012,

Submittal will be approved after the Development package is approved.
01/09/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/12/2012 GERRY KOZIOL WWM REVIEW Denied 1. QUICKTRIP #1461 - NO CREDIT - NO DEMO SHOWN

2. 4" HCS CONNECTION TO EXISTING 8" PUBLIC SEWER IN JUAREZ STREET PER UTILITY PLAN C150 - NEED PCRWRD 1ST FLOOR CHAD AMATEAU REVIEW - 740-6547

3. NEED CAPCITY REVIEW - PCRWRD-3RD FLOOR/KURT STEMM 740-6607

4. NEED WASTEWATER/WC REVIEW OF GREASE INTERCEPTOR - TOM TOMCHAK - 3035 E EL CAMINO DEL CERRO - 724-6200
12/15/2011 DAVE MANN FIRE REVIEW Approved
12/19/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL;
1.For the purpose of assessing additional plan review fees, please submit a written summary of the deferred submittals to the building official, Mr. Ron boose.
2. Please provide approved Site Plan.
SHEET A130
3. Please show roof slopes.
SHEET A530
4. The accessible urinal is to have a 3'-0" wide alcove with a 2'-0" recess as peer ANSI 117.1, Section 605.3 and 305.
5. Details A1 and A6: Please provide elevation references.
SHEET A601
6. Insure all exit doors comply with the 2006 IBC, section 1008.1.9: Panic Hardware.
END OF REVIEW
12/19/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
12/28/2011 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Quick Trip @ 1401 S. Alvernon
T11CM03806 - Building
T11CM03807 - Fuel Canopy
T11BU01653 - Underground Tanks
Building Plan (1st Review)

TRANSMITTAL DATE: December 28, 2011

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until the development package has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
12/29/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
12/29/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A double check valve (e.g. Wilkins model 740) is not acceptable for protecting the water supply to a carbonator. Reference: Section 603.4.12, UPC 2006.
2. If PEX tubing is to be utilized for the hot water recirculation system, provide information showing that the material has been listed by NSF for continuous recirculation applications (e.g. NSF P171 Cl-R). Reference: Sections 301.1.1 and 604.1, UPC 2006.
3. Modify the trap arm lengths (i.e. the note on sheet P101) to conform to Table 10-1, UPC 2006. Reference: Section 1002.2, UPC 2006.
12/29/2011 ROBERT SHERRY WATER REVIEW Approved