Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03594
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/22/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 11/22/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/22/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/23/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. exhaust fan to run whenever air is supplied into the restroom). Reference: Section 403.2.1 (4), IMC 2006. |
| 11/23/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | |
| 11/23/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/23/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/23/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/23/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 11/23/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/23/2011 | RONALD BROWN | ADA | REVIEW | Passed |