Permit Number: T11CM03528
Parcel: 136030770

Address:
8632 E 27TH PL

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T11CM03528
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2011 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

SITE PLAN:

1. Show the water pipe size between the water meter and point of connection for new plumbing. The supply pipe must be sized for the calculated load, 2006 IRC 2903.7.

FLOOR PLANS:

1. Show the location of a minimum 22" x 30" attic access. Attic access is required for areas exceeding 30 SQ FT with a minimum of 30" of headroom and located in a hallway or readily accessible space, R807.1, or show passage between the proposed and accessible existing and attic areas.

STRUCTURAL PLANS:

1. Provide detail for bracing trusses at gable ends to prevent rotation and provide lateral stability, R802.10.3.

SECTIONS - DETAILS:

1. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.
2. Specify water-resistive barrier equivalent to two layers of Grade D paper over the wood based sheathing of exterior plaster wall coverings, R703.6.3.
3. Calculate and show the attic ventilation using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. Account for the existing attic space if removing or blocking existing vents.

PLUMBING PLANS:

1. Provide a water hammer arrester wherever quick-closing valves (clothes washer) are installed in a water distribution system, P2903.5.
2. Clarify the ½" CW notation shown above the water heater on sheet #4. P2903.7. This pipe size is not appropriate for the bathroom supply.
3. Show the water service pipe size with sufficient capacity for controlling excessive flow rates by including a water fixture total for the building, P2903.6. The proposed location adds developed length to the existing water distribution. A minimum 1" service pipe is required for delivering over 9.5 fixture units.

MECHANICAL PLANS:

1. Remove the AC option notation on sheet #7. A revision may be processed if the selected design is altered.
2. Show the location of the AC compressor unit on sheet #7 & 8, M1302.1.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R313.2. Show a smoke alarm on the outside of the bedroom doors.
2. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3602.2.
3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3603.2 and E3801.3 through E3801.4.5.
4. Show the proposed Bathroom receptacle on a 20 AMP circuit, E3603.4.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status