Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03421
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/22/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 1: THE RESIDENTIAL CODE REFERENCES WERE REMOVED, BUT SO WERE ALL OF THE PERTINENT CODES. LIST THE REQUIRED CODES. 2. PREVIOUS COMMENT 2: THE ELECTRICAL, MECHANICAL, PLUMBING, FUEL GAS, EXISTING BUILDING, ETC. REFERENCES WERE REMOVED, BUT SO WERE ALL OF THE PERTINENT CODES. LIST THE REQUIRED CODES. 3. SHEET A1; DETAIL 1: THIS DETAIL IS HARD TO SEE. WHEN SCANNED, IT WILL BE WORSE. ENLARGE THE DETAIL AND DARKEN. 4. SHEET A1; DETAIL AT MAIN COLUMNS: CUT THIS DETAIL ON THE PLAN, AND DARKEN THE DETAIL. 5. PREVIOUS COMMENT 11: THE CODE ANALYSIS MUST BE PROVIDED ON THE DRAWINGS FOR BOTH STRUCTURES, INCLUDING OCCUPANCY CLASSIFICATION, OCCUPANCY LOAD, AND SQUARE FOOTAGES. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/01/2012 | CARL SCHULTZ | FIRE | REVIEW | Approv-Cond | Fire Comments: Provide a fire hydrant or fire sprinklers per IFC 508.5.1 as amended. |
| 05/01/2012 | CARL SCHULTZ | FIRE | REVIEW | Approv-Cond | Fire Flow requirements were determined using NFPA 1142 as referenced in the 2006 IFC. The required 3,175 gallons of storage can be met utilizing the existing water tanks onsite. The owner will provide a proper fire hose connection for firefighter use and sign the area to prevention the connection from being obstructed by the parking of vehicles. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/02/2012 | FERNE RODRIGUEZ | REJECT SHELF | Completed |