Permit Number: T11CM03421
Parcel: 13631002P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03421
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 1: THE RESIDENTIAL CODE REFERENCES WERE REMOVED, BUT SO WERE ALL OF THE PERTINENT CODES. LIST THE REQUIRED CODES.
2. PREVIOUS COMMENT 2: THE ELECTRICAL, MECHANICAL, PLUMBING, FUEL GAS, EXISTING BUILDING, ETC. REFERENCES WERE REMOVED, BUT SO WERE ALL OF THE PERTINENT CODES. LIST THE REQUIRED CODES.
3. SHEET A1; DETAIL 1: THIS DETAIL IS HARD TO SEE. WHEN SCANNED, IT WILL BE WORSE. ENLARGE THE DETAIL AND DARKEN.
4. SHEET A1; DETAIL AT MAIN COLUMNS: CUT THIS DETAIL ON THE PLAN, AND DARKEN THE DETAIL.
5. PREVIOUS COMMENT 11: THE CODE ANALYSIS MUST BE PROVIDED ON THE DRAWINGS FOR BOTH STRUCTURES, INCLUDING OCCUPANCY CLASSIFICATION, OCCUPANCY LOAD, AND SQUARE FOOTAGES.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/01/2012 CARL SCHULTZ FIRE REVIEW Approv-Cond Fire Comments:

Provide a fire hydrant or fire sprinklers per IFC 508.5.1 as amended.
05/01/2012 CARL SCHULTZ FIRE REVIEW Approv-Cond Fire Flow requirements were determined using NFPA 1142 as referenced in the 2006 IFC. The required 3,175 gallons of storage can be met utilizing the existing water tanks onsite. The owner will provide a proper fire hose connection for firefighter use and sign the area to prevention the connection from being obstructed by the parking of vehicles.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/02/2012 FERNE RODRIGUEZ REJECT SHELF Completed