Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T11CM03421
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T1; CODES: REMOVE ALL REFERENCES TO THE RESIDENTIAL CODE AND INCLUSIVE HOME DESIGN ORDINANCE. ADD THE ACCESSIBILITY CODE ICC/ANSI A117.1-2003. 2. SHEET T1; CODES: REMOVE ALL REFERENCES TO CODES THAT ARE NOT PERTINENT TO THIS PROJECT (ELECTRICAL, MECHANICAL, PLUMBING, FUEL GAS, EXISTING BUILDING, ETC.). 3. SHEET A; GENERAL NOTES: PROVIDE MATERIAL PROPERTIES FOR CONCRETE AND CONCRETE REINFORCEMENT. 4. SHEET A; BUILDING LOADS: PROVIDE THE GEOTECHNICAL INFORMATION USED FOR THE FOUNDATION DESIGN (WRITTEN REPORT OR ASSUMED VALUE PER THE IBC.). 5. SHEET A; GENERAL NOTES: REMOVE ALL REFERENCES TO ORGANIZATIONS AND CODES THAT ARE NOT PERTINENT TO THIS PROJECT (WELDING, ICBO/UBC, SOUTHERN BUILDING CODE, BOCA, NATIONAL CODE OF CANADA, ETC.). 6. SHEET A1: PROVIDE A DETAIL FOR THE FOUNDATION AT THE SLAB EDGE. 7. SHEET A1: PROVIDE A DETAIL FOR THE FOUNDATION AT THE ENDWALL COLUMNS. 8. SHEET A1.2 (CROSS SECTION); STRUCTURAL CALCULATIONS: THE COLUMN SECTION INDICATED ON SHEET A1.2 (8X3.5, 16 GA.) DOES NOT APPEAR IN THE CALCULATIONS (8X3.5, 14 GA. OR 8X2.5, 14 GA.). CLARIFY. 9. GENERAL: THE ROOF PANEL AND WALL PANEL SIZES ARE NOT INDICATED ON THE DRAWINGS. PROVIDE PER THE CALCULATIONS. 10. GENERAL: PLANS, ELEVATIONS, SECTIONS, DETAILS, NOTES, SPECIFICATIONS, AND MATERIAL PROPERTIES FOR THE SHADE STRUCTURE MUST BE INCLUDED ON FULL SIZE SHEETS. 11. GENERAL: PROVIDE A CODE ANALYSIS ON THE DRAWINGS FOR BOTH STRUCTURES, INDICATING OCCUPANCY CLASSIFICATION, OCCUPANCY LOAD, AND CONSTRUCTION CLASSIFICATION. 12. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 01/04/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 01/04/2012 | ROBERT SHERRY | ELECTRICAL-COMMERCIAL | REVIEW | Passed | No electrical work shown on drawings. |
| 01/04/2012 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 01/04/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 01/04/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/04/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 12/22/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | Fire Comments: Provide a fire hydrant or fire sprinklers per IFC 508.5.1 as amended. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/09/2012 | CPIERCE1 | REJECT SHELF | Completed |