Permit Number: T11CM03269
Parcel: 14022003K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03269
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2011 GERRY KOZIOL WWM REVIEW Approved
11/16/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/16/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The UPC requires the scupper width be at least equal to the circumference of the roof drain size determined by Table 11-1. See Section 1101.11.2.1, UPC 2006. [Original comment: Provide sizing information for the roof scupper. Reference: Section 1101.11.2.1 and Table 11-1, UPC 2006.]
11/21/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/22/2011 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
11/22/2011 SUE REEVES REJECT SHELF Completed