Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03269
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/15/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/16/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/16/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The UPC requires the scupper width be at least equal to the circumference of the roof drain size determined by Table 11-1. See Section 1101.11.2.1, UPC 2006. [Original comment: Provide sizing information for the roof scupper. Reference: Section 1101.11.2.1 and Table 11-1, UPC 2006.] |
| 11/21/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/22/2011 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
| 11/22/2011 | SUE REEVES | REJECT SHELF | Completed |