Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM03219
Parcel: 133243700

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03219
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/21/2011 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. show size and direction of waste piping exiting GT-1 and connecting to sanitary sewer. Show how GT-1 is to be vented. Reference: 907.1 2006 IPC. 2. Show how the interceptor is to be installed on the washing machine drain. Reference: 1003.6 2006 IPC. 3. Clothes washer drain connected to grease waste. Reference 1003.2, and 1003.3.1 2006 IPC. Non grease producing fixtures shall not discharge through the interceptor. 4. Revise the site drawing to include the following information: the location and size of the water meter
b.the location of the main water lines and fire hydrants
c The location of the gas meter
d.the location and size of the public sanitary sewer and
the location, invert, and rim elevation of all manholes and cleanouts.
Reference: City of Tucson Development Standard No. 2-01.1.0 2 3.8 D provide watercaculations. Provide the method of sterilization. Reference: 610 2006 IPC.
10/21/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/21/2011 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved per Robert Sherry

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2011 CPIERCE1 OUT TO CUSTOMER Completed
10/27/2011 SUE REEVES REJECT SHELF Completed