Permit Number: T11CM03209
Parcel: 13824101K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03209
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2011 ROBERT SHERRY WATER REVIEW Approved
12/02/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Second request: revise the font size used on the drawings to a minimum of 3/32-inch high (see sheet P1.1). Reference: Section 106.1.1, IBC 2006.
2. Comment not resolved; a 2" cleanout is not approved for use with a 3" drain pipe. [Original comment: Show the size of the under-floor portion of the vents for the floor sinks located in the equipment room and in the sales floor area. The size of that portion of the vent shall comply with the cleanout size requirements of Table 7-6, UPC 2006. Reference: Section 707.11, UPC 2006.]
3. Comment not resolved; the waste and vent schematic shows a mop sink and a floor drain without flow control devices. [Original comment: Each fixture that is connected to a hydromechanical grease interceptor requires a flow control device unless the grease interceptor is equipped with an integral flow control device. Reference: Section 1014.2.1, UPC 2006.]
4. Coordinate the location of the entry point for the water service to the building: civil sheet 4 of 12 (Utility plan) and P1.1 show different entry locations. Reference: Section 103.2.3, UPC 2006.
12/07/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Need Approved Site Plan.
2. Need County Health Department activity number.
SHEET NUMBERS A9.4 AND S4.1
3. Detail numbers 1/A9.4 and 108/S4.1 are the same detail but are contradictory to each other. Please reconcile.
END OF REVIEW
12/09/2011 DAVID RIVERA ZONING REVIEW Denied The Development Plan is still under review through the CDRC Review Process. As of this review date 12/9/11, the development plan has not been approved. Zoning will re-review the building plans on the next submittal and compare the building plans to the approved development plan. Zoning will review the building plans to ensure compliance with the approved development plan if the DP has been approved and stamped by the CDRC manager. If available include a copy of the approved DP on the building submittal. Additional comments may be forthcoming.
12/15/2011 GERRY KOZIOL WWM REVIEW Denied NEED CIVAL DRAWINGS (SITE & UTILITY PLANS) SHOWING LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - NEED PCRWRD 1ST FLOOR / CHAD AMATEAU REVIEW OF LOCATION/METHOD OF CONNECTION - 740-6547
NEED WW/IWC REVIEW & APPROVAL OF GREASE TRAP - TOM TOMCHAK - 5025 W INA RD - 443-6200
NEED 5TH FLOOR WW CREDIT EVALUATION FOR DEMO OF EXSISTING BLDG. 740-6602 OR 740-6606
12/29/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/04/2012 FERNE RODRIGUEZ REJECT SHELF Completed
01/03/2012 CPIERCE1 OUT TO CUSTOMER Completed