Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03091
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/27/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/27/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/27/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 09/27/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/27/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/27/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/27/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/03/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 11/03/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Section 802.1, IPC 2006. 2. Provide a detail showing how the flow control device for the grease intercepter will be installed. 3. Provide backflow protection for the appliances connected directly to the water supply. 4. Provide a detail for the installation of the water heater, including the expansion tank, shut off valve, and the T&P relief. |
| 11/03/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical Review: Provide circuit breaker sizes for all circuits in the panel schedule. The loads shown are incorrect, in some circuits the plan shows 120 volt outlets with 3000va loads which equal 25 amps,these should be 20 amps or less.Some light and sign circuits are shown at 3000 va(wats) these are 20 amp circuits. In general the load calculations need to be revised. Ray Majuta Elect Plan Review PDSD, CoT 11/3/11 |
| 11/04/2011 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 11/04/2011 | CPIERCE1 | DRB | REVIEW | Needs Review |