Permit Number: T11CM03091
Parcel: 117120200

Address:
39 N 6TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03091
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
09/27/2011 ROBERT SHERRY WATER REVIEW Approved
09/27/2011 ERIC NEWCOMB ADA REVIEW Passed
09/27/2011 LOREN MAKUS ENGINEERING REVIEW Approved
09/27/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/27/2011 DAVE MANN FIRE REVIEW Approved
09/27/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/03/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/03/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Section 802.1, IPC 2006.
2. Provide a detail showing how the flow control device for the grease intercepter will be installed.
3. Provide backflow protection for the appliances connected directly to the water supply.
4. Provide a detail for the installation of the water heater, including the expansion tank, shut off valve, and the T&P relief.
11/03/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical Review: Provide circuit breaker sizes for all circuits in the panel schedule. The loads shown are incorrect, in some circuits the plan shows 120 volt outlets with 3000va loads which equal 25 amps,these should be 20 amps or less.Some light and sign circuits are shown at 3000
va(wats) these are 20 amp circuits. In general the load calculations need to be revised.

Ray Majuta
Elect Plan Review
PDSD, CoT
11/3/11
11/04/2011 CPIERCE1 WWM REVIEW Needs Review
11/04/2011 CPIERCE1 DRB REVIEW Needs Review