Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02933
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/12/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/12/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the barber shop meets the ventilation requirements of Section 403.3, IMC 2006. |
| 09/12/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/12/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/12/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/12/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/12/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. A hair trap and a p-trap cannot be located on the same trap arm. You may use one or the other; not both. 2. The "PRV" called out for the water heater should be a temperature and pressure relief (T&P). 3. Showhow the water temperature for the lavatory will be limited to 110 degrees Fahrenheit. 4. Show the shut-off valve for the water heater. The expansion tank shall be located between the shut-off valve and the water heater. 5. The vent for the sinks shall rise 6" above the flood rim of the sinks prior to running horizontal. |
| 09/12/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 09/12/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/12/2011 | RONALD BROWN | ADA | REVIEW | Passed | |