Permit Number: T11CM02933
Parcel: 11449042N

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02933
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
09/12/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the barber shop meets the ventilation requirements of Section 403.3, IMC 2006.
09/12/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/12/2011 ROBERT SHERRY WATER REVIEW Approved
09/12/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/12/2011 GERRY KOZIOL WWM REVIEW Approved
09/12/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A hair trap and a p-trap cannot be located on the same trap arm. You may use one or the other; not both.
2. The "PRV" called out for the water heater should be a temperature and pressure relief (T&P).
3. Showhow the water temperature for the lavatory will be limited to 110 degrees Fahrenheit.
4. Show the shut-off valve for the water heater. The expansion tank shall be located between the shut-off valve and the water heater.
5. The vent for the sinks shall rise 6" above the flood rim of the sinks prior to running horizontal.
09/12/2011 PAUL MACHADO ENGINEERING REVIEW Approved
09/12/2011 DAVE MANN FIRE REVIEW Approved
09/12/2011 RONALD BROWN ADA REVIEW Passed
09/12/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed