Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM02899
Parcel: 132130690

Review Status: Completed

Review Details: REVISION - - 4TH

Permit Number - T11CM02899
Review Name: REVISION - - 4TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/07/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/10/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/27/2012 CPIERCE1 APPROVAL SHELF Completed
09/27/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed