Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 4TH
Permit Number - T11CM02899
Review Name: REVISION - - 4TH
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/14/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/21/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
06/21/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; the proposed Type II hood is located over the double-oven (K10) but not the rapid-cook oven (K12) or the microwave oven (K14). If the hood is large enough to cover both K-10 and K12, then K-14 will fall under exception 3 of Section 507.2.2, IMC 2006 and it will not require a hood. [Original comment: Provide a Type II hood over the three bread ovens and microwave oven. Section 507.2.2, IMC 2006, exception 3, allows the installation of a "single light-duty electric convection, bread, retherm, or microwave oven" without the requirement of installing a Type II hood.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/26/2012 | CINDY AGUILAR | APPROVAL SHELF | Completed |
06/26/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |