Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM02899
Parcel: 132130690

Review Status: Completed

Review Details: REVISION - - 4TH

Permit Number - T11CM02899
Review Name: REVISION - - 4TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/21/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/21/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; the proposed Type II hood is located over the double-oven (K10) but not the rapid-cook oven (K12) or the microwave oven (K14). If the hood is large enough to cover both K-10 and K12, then K-14 will fall under exception 3 of Section 507.2.2, IMC 2006 and it will not require a hood. [Original comment: Provide a Type II hood over the three bread ovens and microwave oven. Section 507.2.2, IMC 2006, exception 3, allows the installation of a "single light-duty electric convection, bread, retherm, or microwave oven" without the requirement of installing a Type II hood.]

Final Status

Task End Date Reviewer's Name Type of Review Description
06/26/2012 CINDY AGUILAR APPROVAL SHELF Completed
06/26/2012 CINDY AGUILAR OUT TO CUSTOMER Completed