Permit Number: T11CM02899
Parcel: 132130690

Review Status: Completed

Review Details: REVISION - - 4TH

Permit Number - T11CM02899
Review Name: REVISION - - 4TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a Type II hood over the three bread ovens and microwave oven. Section 507.2.2, IMC 2006, exception 3, allows the installation of a "single light-duty electric convection, bread, retherm, or microwave oven" without the requirement of installing a Type II hood.
05/08/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide direct waste connections for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.
2. A double check valve is not acceptable for protecting the water supply to a carbonator; provide a reduced pressure backflow preventer. Reference: Section 603.4.12, UPC 2006.
05/10/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET C1; OCCUPANCY LOAD CALCULATIONS: THE CALCULATIONS ON THE LEFT (OCCUPANCY LOAD CALCULATIONS) INDICATE 4354 TOTAL OCCUPANTS, WHILE THE TABLE ON THE RIGHT (ACCESSORY EGRESS WIDTH CALCULATIONS) INDICATES 4228 OCCUPANTS. CLARIFY.
2. SHEET C1; PLUMBING FIXTURE COUNTS: THIS TABLE INDICATES AN OCCUPANCY LOAD OF 4376. SEE COMMENT 1.
3. SHEET A1; FLOOR PLAN: SHOW THE NEW TENANT SPACE ON THIS PLAN (OR INDICATE WITH A NOTE).
4. SHEET A5.1; FOOD TENANT PLAN 3: ARE ANY OF THE DETAILS OR SECTIONS INDICATED ON THIS PLAN NEW DUE TO THE ADDITION OF A TENANT IN THE SPACE? IF SO, INCLUDE SHEET A6.2 IN THIS PERMIT SET.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/10/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/12/2012 CINDY AGUILAR APPROVAL SHELF Completed
06/12/2012 CINDY AGUILAR OUT TO CUSTOMER Completed