Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 4TH
Permit Number - T11CM02899
Review Name: REVISION - - 4TH
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide a Type II hood over the three bread ovens and microwave oven. Section 507.2.2, IMC 2006, exception 3, allows the installation of a "single light-duty electric convection, bread, retherm, or microwave oven" without the requirement of installing a Type II hood. |
| 05/08/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide direct waste connections for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006. 2. A double check valve is not acceptable for protecting the water supply to a carbonator; provide a reduced pressure backflow preventer. Reference: Section 603.4.12, UPC 2006. |
| 05/10/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET C1; OCCUPANCY LOAD CALCULATIONS: THE CALCULATIONS ON THE LEFT (OCCUPANCY LOAD CALCULATIONS) INDICATE 4354 TOTAL OCCUPANTS, WHILE THE TABLE ON THE RIGHT (ACCESSORY EGRESS WIDTH CALCULATIONS) INDICATES 4228 OCCUPANTS. CLARIFY. 2. SHEET C1; PLUMBING FIXTURE COUNTS: THIS TABLE INDICATES AN OCCUPANCY LOAD OF 4376. SEE COMMENT 1. 3. SHEET A1; FLOOR PLAN: SHOW THE NEW TENANT SPACE ON THIS PLAN (OR INDICATE WITH A NOTE). 4. SHEET A5.1; FOOD TENANT PLAN 3: ARE ANY OF THE DETAILS OR SECTIONS INDICATED ON THIS PLAN NEW DUE TO THE ADDITION OF A TENANT IN THE SPACE? IF SO, INCLUDE SHEET A6.2 IN THIS PERMIT SET. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/10/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/12/2012 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 06/12/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |