Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM02798
Parcel: 105102450

Address:
565 E WETMORE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02798
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2011 STEVE SHIELDS ZONING REVIEW Approved
08/29/2011 JASON GREEN ENGINEERING REVIEW Approved
08/29/2011 ERIC NEWCOMB ADA REVIEW Passed
08/29/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-101: NOTE 14 INDICATES TO RETAIN THE EXISTING GRAB BARS. PROVIDE A DETIAL ON THE DRAWINGS INDICATING GRAB BAR AND DISPENSER LOCATION PER THE ICC/ANSI FIGURES 604.5.1, 604.5.2, AND 604.7.
2. SHEETS A-103, A-104, AND A-201; DRAWING NOTES: REFERENCE IS MADE TO AN AUGUST 2010 MANUAL FOR TYPICAL SPECIFICATIONS AND DETAILS. PROVIDE THOSE THAT ARE PERTINENT TO THIS PROJECT.
3. SHEET A-104: IBC SECTION 1109.11 REQUIRES 5% OF SEATING/STANDING SPACE TO BE ACCESSIBLE. INDICATE THOSE LOCATIONS ON THE PLAN.
4. SHEET A-201; NOTE 17: THE INTERIOR WALL MUST MEET THE IBC SECTION 1607.13 FOR HORIZONTAL LOADING. PROVIDE A DETAIL INDICATING BRACING SIZE AND SPACING AT THE TOP OF THE WALL. SHOW THE CONNECTION DETAIL OF THE BRACE TO THE TOP OF THE WALL AND TO THE EXISTING ROOF STRUCTURE.
08/29/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/30/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/30/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/30/2011 ROBERT SHERRY WATER REVIEW Approved
08/30/2011 DAVE MANN FIRE REVIEW Approved
08/30/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical notes: Sheet A 001 indicates quite a few of the light fixtures are tro be changed out, make a notation indicating loads changes.If all fixtures are to lower loads notate, if the loads will be increased also notate on sheet.


RT Majuta
El PLn Ck
PDSD, 8/30/11
09/07/2011 CAGUILA1 WWM REVIEW Needs Review