Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02798
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/29/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/29/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
08/29/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
08/29/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A-101: NOTE 14 INDICATES TO RETAIN THE EXISTING GRAB BARS. PROVIDE A DETIAL ON THE DRAWINGS INDICATING GRAB BAR AND DISPENSER LOCATION PER THE ICC/ANSI FIGURES 604.5.1, 604.5.2, AND 604.7. 2. SHEETS A-103, A-104, AND A-201; DRAWING NOTES: REFERENCE IS MADE TO AN AUGUST 2010 MANUAL FOR TYPICAL SPECIFICATIONS AND DETAILS. PROVIDE THOSE THAT ARE PERTINENT TO THIS PROJECT. 3. SHEET A-104: IBC SECTION 1109.11 REQUIRES 5% OF SEATING/STANDING SPACE TO BE ACCESSIBLE. INDICATE THOSE LOCATIONS ON THE PLAN. 4. SHEET A-201; NOTE 17: THE INTERIOR WALL MUST MEET THE IBC SECTION 1607.13 FOR HORIZONTAL LOADING. PROVIDE A DETAIL INDICATING BRACING SIZE AND SPACING AT THE TOP OF THE WALL. SHOW THE CONNECTION DETAIL OF THE BRACE TO THE TOP OF THE WALL AND TO THE EXISTING ROOF STRUCTURE. |
08/29/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/30/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
08/30/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
08/30/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/30/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
08/30/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical notes: Sheet A 001 indicates quite a few of the light fixtures are tro be changed out, make a notation indicating loads changes.If all fixtures are to lower loads notate, if the loads will be increased also notate on sheet. RT Majuta El PLn Ck PDSD, 8/30/11 |
09/07/2011 | CAGUILA1 | WWM | REVIEW | Needs Review |