Permit Number: T11CM02529
Parcel: 13225069G

Review Status: Completed

Review Details: SITE

Permit Number - T11CM02529
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2011 ENEWCOM1 ZONING REVIEW Approved
08/24/2011 ANDREW CONNOR NPPO REVIEW Approved
08/24/2011 ANDREW CONNOR LANDSCAPE REVIEW Approved
08/24/2011 JASON GREEN ENGINEERING REVIEW Approved
08/25/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter
b. the location of the main water lines to the address and fire hydrants
c. the location of the on-site sewage disposal system (septic tank, leach field, back-up leach field)
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
08/25/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Sheet A100

1. Provide seal on this sheet. Building Data and Egress are profession practice.

2. Show locations of fire hydrants. See IFC Sections 508 and Appendix B for fire flow for new area.

3. Show fire lanes. Show locations of gates, etc. Arials show the site as congested. Fire lanes may need signs. See IFC Section 503 as amended.

4. Provide quantities of hazardous materials. Will they increase with this addition? See IFC Chapter 27.
08/25/2011 LHANLY1 ADA REVIEW Passed
08/25/2011 LEERAY HANLY H/C SITE REVIEW Denied NOT ENOUGH INFORMATION HAS BEEN PROVIDED ON THIS PLAN SET TO DETERMINE COMPLIANCE WITH ANY EXISTING OR REQUIRED ACCESSIBLE COMPONENTS.

1) SHOW ALL ACCESSIBLE ROUTES
2) SHOW ALL ACCESSIBLE PARKING

Final Status

Task End Date Reviewer's Name Type of Review Description
09/14/2011 CPIERCE1 OUT TO CUSTOMER Completed