| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/07/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Sheet E501 shows the new 400 amp sevice using 312.5 amps ( Demand load) being added to an existing service gutter. There are three other existing services on this main service. These is no other information concerning this. What ampacity is the existing service ? What will the total ampacity equal concerning the existing amperage on the service plus the ampacity used by this tenant? What will the fault currentbe on the 400 amp disconnect and the new panels. I apologize with was not requested last review, have just noticed that this information needs to be reviewed and verified. Ray T Majuta, Elect Plan Review, PDSD, C of Tucson, 10/07/11 Raymajuta@tucsonaz.gov |
| 10/18/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/18/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/18/2011 | ROBERT SHERRY | WATER | REVIEW | Approved |