Permit Number: T11CM02486
Parcel: 13322500G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02486
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/15/2011 ROBERT SHERRY WATER REVIEW Denied 1. Comment not addressed. Provide a site utility plan showing the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code. http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf
2. Comment not addressed. Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006.
09/15/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed; see section 403.3.2, IMC 2006 for instructions regarding the common ventilation system. [Original comment: Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2006.]
09/15/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved. Provide a natural gas piping design, showing the gas pressures, pipe sizes, control valves, loads and developed lengths of the piping.[Original comment: Provide a natural gas piping design, including the piping layout on a floor plan and a natural gas schematic showing the gas pressures, pipe sizes, control valves, loads and developed lengths of the piping. Reference: Section 106.3.1, IFGC 2006.]
10/03/2011 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review