Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM02486
Parcel: 13322500G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02486
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2011 JASON GREEN ENGINEERING REVIEW Approved
08/19/2011 GERRY KOZIOL WWM REVIEW Approved
08/30/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. The City of Tucson has not adopted the 2009 North Carolina Plumbing Code. The appropriate codes and their local amendments can be found under the Department of Planning and Development Services on the City of Tucson web site, www.tucsonaz.gov.
3. Provide a natural gas piping design, including the piping layout on a floor plan and a natural gas schematic showing the gas pressures, pipe sizes, control valves, loads and developed lengths of the piping. Reference: Section 106.3.1, IFGC 2006.
4. Clarify the apparent conflict between Plumbing General Note #17 and Plumbing Specification #25 with respect to the required insulation for recirculating hot water piping. Reference: Section 504.5, IEEC 2006.
08/30/2011 ROBERT SHERRY WATER REVIEW Denied 1. Provide a site utility plan showing the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code. http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf
2. Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006.
08/30/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Clarify how all ductwork installation is to comply with the requirements of "Chapter 5 of the Mechanical Code". Reference: Section 106.3.1, IMC 2006.
3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006.
4. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson.
5. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or above grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.
6. Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2006.
09/01/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET G202; DETAIL 2: PROVIDE A VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003, FIGURE 604.5.1.
2. SHEET G202; DETAIL 2: LOCATE THE PAPER DISPENSER PER ICC/ANSI A117.1-2003, FIGURE 604.5.1.
3. SHEETS G202 AND G203: THESE SHEETS ARE ONLY PROVIDED IN ONE SET OF REVIEW DRAWINGS. ADD THESE SHEETS TO THE SECOND SET.
09/14/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM02486
7119 E Broadway Bl
TI Medical Bldg

The electrical plans have been denied for the following:
1. Sheet E201 indicates on Special Hex Notes # 5, "provide shunt trip breaker at PNL PP1" is this a mis-print,where is PNL PP?
2. Sheet E201, "Supply Power To J-Box A" at bottom right of sheet indicates the load for CT to be 480vac, 3 phase, 70kva, peak 154 amps. The circuit appointed for the disconnect shows going to MDP 19,21 in the panel schedule ? The note in the information box states, " Distribution Transformer", explane this.
3. Provide 2006 IECC Lighting Budget Calculations.
4. As per City of Tucson Commercial Submittal Requirements, panel total loads for each phase (Panel MDP) are required to be within 15% .

Ray Majuta,
Elect Pln CK,PSDS,
City of Tucson,
9/14///
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
09/14/2011 SUE REEVES REJECT SHELF Completed