Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM02300
Parcel: 13304003A

Review Status: Completed

Review Details: OTHER

Permit Number - T11CM02300
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2011 LOREN MAKUS ENGINEERING REVIEW Approved
08/02/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied 1) please reference NEC 250.52 for electrode grounds, I do not belive the word U-fer appears in the NEC.

2) Does well wiring come from panel H1 as indicated; or are you tapping in the new gutter?

3) What is minimum ISC rating of equipement?

4) Where are receps being fed from?

5) Please clarify where panel H1 is at, also label new 125 panel and show its loads....or is it panel H1? In which case you have it identified as both a 200A panel and a 125A panel.

6) Show all panel locations.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/02/2011 CPIERCE1 OUT TO CUSTOMER Completed