Permit Number: T11CM02063
Parcel: 105110630

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02063
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2011 GERRY KOZIOL WWM REVIEW Approved
07/01/2011 RONALD BROWN ADA REVIEW Passed
07/01/2011 MARTIN BROWN FIRE REVIEW Approved
07/08/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. As per the 2006 IBC, Section 1109.12.1, at least one dressing room must be accessible. Please provide detailing showing accessibility clearances, accessory mounting heights, mirrors and seating as required.
2. Please provide structural calculations for the wall mounted water heater bracket assembly.
3. The electrical drawings have lettering smaller than COT standards of 3/32". Please make changes and resubmit.
END OF REVIEW
07/18/2011 ROBERT SHERRY WATER REVIEW Approved
07/18/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The City of Tucson allows either the 2006 International Plumbing Code or the 2006 Uniform Plumbing Code to be used for the minimum basis of design but not both codes. The architectural title sheet lists both codes as applicable and the plumbing drawings appear to have been designed primarily per the 2006 UPC with portions based on the 2006 IPC. The plumbing drawings have been reviewed to the 2006 UPC as amended by the City of Tucson.
2. Provide a vacuum relief valve for the water heater. Reference: Section 608.7, UPC 2006.
3. Provide cleanouts that are the same nominal size as the pipes that they serve. Reference: Section 707.11, UPC 2006.
07/18/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson.
2. Confirm the sequence of operation for the restroom exhaust fans results in all of the air supplied to the restrooms being exhausted (i.e. the exhaust fans are to run whenever air is being supplied to the restroom). The mechanical plans call for an independent switch for each fan but the electrical plans call for the exhaust fans to be interconnected with the room lights. Reference: Section 403.2.1 (4), IMC 2006.
07/20/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM02063
4230 N Oracle Rd # 180
TI Retail

1. All lettering and numbering to min 3/32", see electrical sheels.
2. The sequence of operation for exhaust and supply of exhaust fan and supplied air in restrooms,to b interlocked,
see Mechanical Plans Examiner comments.

Ray T Majuta,
Elect Plns Ck,PDSD,
City of Tucson,
7/23/11
Ray.majuta@tucsonaz.gov
07/26/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
07/28/2011 SUE REEVES REJECT SHELF Completed