Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T11CM01742
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/01/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/06/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. FAMILY DOLLAR - ADDITON/REMODEL 2. NEED CLEARLY IDENTIFY ALL PLUMBING FIXTURES IN EXISTING ELECTRICAL RM - DRAWINGS SHOW EXISTING PLUMBING LINE IN ELECT RM - RECOUNTED ALL WASTEWATER PLUMBING FIXTURES - NEED 5TH FLOOR CREDIT EVALUTION 4. NEED TO SHOW LOCATION/METHOD OF EXISTING CONNECTION TO PUBLIC SEWER - LOT RECONFIGURATION |
07/08/2011 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Family Dollar - Broadway & Plumer T11CM01742 Building Plan (2nd Review) TRANSMITTAL DATE: July 8, 2011 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning can not approve the building plan until the Site plan has been approved. 3. As the site, landscape & building plans have been submitted together combine the plans together and revise the drawing index to reflect all sheets as one set prior to the next submittal. 4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved Site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\bldg\t11cm01742.doc |
07/08/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
07/08/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Resubmitted, revised drawing sets are incomplete. Please provide two complete sets of construction documents and drawings including all revisions for all disciplines. 2. Please rework your General Building Summary using the new square footages provided. a. This includes actual building area, occupant load, and toilet fixture counts. END OF REVIEW |
07/12/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/12/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; the new drawing sets contain only sheet S-3.0 and do not have any referenced structural details. Include all seven of the structural sheets as shown in the project index. [Original comment: Provide information (e.g. architectural details) to show how the proposed water heater is to be supported from the building structure. Reference: Section 314.5, UPC 2006.] 2. Comment not resolved; the "existing" roof drain and overflow drain shown on sheet P1.0 are not in the same location that they are shown in on the roof plan (A3.1) or on the aerial photograph. On sheet A3.1, the new addition has its own roof drain and overflow drain. Coordinate the roof drainage with the building design. [Original comment: Provide roof drainage calculations and plans. Reference: Section 1101, IPC 2006.] |
07/14/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/19/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
07/19/2011 | SUE REEVES | REJECT SHELF | Completed |