Permit Number: T11CM01588
Parcel: 13104399H

Address:
4777 E 29TH ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T11CM01588
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2011 RONALD BROWN ADA REVIEW Passed
09/01/2011 GERRY KOZIOL WWM REVIEW Approved
09/06/2011 DAVE MANN FIRE REVIEW Approved
09/07/2011 JASON GREEN ENGINEERING REVIEW Approved Building Only
09/09/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved. The proposed 3" diameter openings located in two sides of each collector box do not have the same flow capacity as the minimum required scupper. The openings act as weirs, not vertical pipes (or horizontal pipes running full) and the pipe sizes obtained from Table 1106.2 or Table 1106.3, IPC 2006 are not correct. In addition, the projected roof area you provide does not appear to include the effect of surrounding vertical walls (i.e. parapets) that can divert rain onto the roof (Section 1106.4, IPC 2006). [Original comment: Provide calculations to show that the size of the two overflow openings in the roof drain collector boxes have a drainage capacity equal to the minimum required scupper size. Reference: Section 1107.1, IPC 2006.]
09/09/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/09/2011 STEVE SHIELDS ZONING REVIEW Approved
09/09/2011 ROBERT SHERRY WATER REVIEW Approved
09/12/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/12/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approv-Cond Reference plumbing for overflow flow drain comments.
09/12/2011 RONALD BROWN ZONING HC REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2011 CPIERCE1 OUT TO CUSTOMER Completed
09/13/2011 SUE REEVES REJECT SHELF Completed